| 2022-10-18 12:10:22 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMEND 107.3.5.3 (13) - PLEASE SUBMIT A SITE |
| | PLAN SHOWING ALL THE REQUIRED SETBACKS (PLEASE NOTE THE |
| | GENERATOR IS REQUIRED TO BE AT LEAST 10 FEET FROM |
| | STRUCTURE OPENINGS). |
| | |
| | 2. 2017 WPB AMEND 107.3.5.3 (13) - PLEASE SUBMIT THE |
| | GAS RISER. INCLUDE THE EXISTING SYSTEM'S LAYOUT WITH |
| | PIPE SIZES, BTU LOADS, PIPING MATERIALS, TYPE OF GAS, |
| | LOCATION OF SHUT OFFS, AND ANYTHING ELSE YOU MIGHT BE |
| | ABLE TO PROVIDE TO SHOW CODE COMPLIANCE. |
| | |
| | 3. 2017 WPB AMENDS 107.2.1 - PLEASE MAKE SURE THE |
| | PERSON WHO DESIGNS THE DRAWING PRINTS THEIR NAME, SIGNS |
| | THEIR NAME, AS WELL AS PUTS YOUR CONTRACTOR NUMBER ON |
| | THE DRAWING AS REQUIRED BY THE WEST PALM BEACH |
| | AMENDMENTS TO CHAPTER 1. |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | REFERENCED CODES: |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |