Plan Review Notes
Plan Review Notes For Permit 22090848
Permit Number 22090848
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-10-11 13:24:03FIRE REVIEW COMMENTS:
  
 PROVIDE A DETAILED SITE PLAN INDICATING DISTANCE TO ANY
 STRUCTURES, AND MINIMUM CLEARANCES ON ALL SIDES OF THE
 PROPOSED GENERATOR TO COMPLY WITH NFPA 110.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  