| Plan Review Notes For Permit 22090842 |
| Permit Number |
22090842 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-31 07:45:19 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 625.43 DISCONNECTING MEANS. | | | | | | FOR EQUIPMENT RATED MORE THAN 60 AMPERES OR MORE THAN | | | 150 VOLTS TO GROUND, THE DISCONNECTING MEANS SHALL BE | | | PROVIDED AND INSTALLED IN A READILY ACCESSIBLE | | | LOCATION. THE DISCONNECTING MEANS SHALL BE LOCKABLE | | | OPEN IN ACCORDANCE WITH 110.25 |
|