| 2022-10-18 10:22:17 | 1ST REVIEW FMC | | | PERMIT: 22090720 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE A SCOPE OF WORK FOR THE MECHANICAL DESIGN. | | | FBC 107.3.5 | | | | | | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR THIS PROJECT. FEC C403.2.1 | | | | | | 3) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS | | | PROJECT. FMC 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | 4) PROVIDE A MECHANICAL DEMO PLAN FOR THE WORK BEING | | | REMOVED OR CHANGED. FBC 107.3.5 | | | | | | 5) PROVIDE INFORMATION FOR THE MECHANICAL SYSTEMS | | | SHOWING THEM MEET THE SPACE HEATING REQUIREMENTS OF FMC | | | 309.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|