| 2022-10-05 14:50:27 | ELECTRIC REVIEW FAILED |
| | 1) PLEASE PROVIDE DETAILS AS TO LOCATION OF ALL POWER |
| | PACKS (IT APPEARS ONLY 2 ARE SHOWN). IN ADDITION PLEASE |
| | PROVIDE FLOOR PLAN DETAILING LOCATION OF ELECTRIC |
| | PANEL(S) FEEDING POWER PACKS, PANEL SCHEDULES , LOAD |
| | CALCULATIONS FOR UPSTREAM PANEL(S) AND OVERCURRENT |
| | PROTECTION. |
| | 2) PLEASE CLARIFY IF THE UNITS OPERATE HYDRAULICALLY OR |
| | ELECTRICALLY AS THE SPECIFICATIONS LACK CLARITY AS TO |
| | THEIR OPERATION. SPECIFICATIONS PROVIDED DETAIL (3) 16 |
| | AMP DELAYED ACTION MAIN FUSES PER UNIT. IF UNITS ARE |
| | INDIVIDUALLY ELECTRICLY POWERED , PLEASE PROVIDE |
| | DETAILS ON ALL 208 VOLT CONDUIT AND CONDUCTOR RUNS. IF |
| | HYDAULICALLY OPERATED PROVIDE DETAILS OF HYDRAULIC |
| | LINES. |
| | 3) PLEASE PROVIDE CLARITY ON CACULATION DOCUMENTS |
| | PROVIDED STATING THAT 21 CAR LIFTS WILL BE INSTALLED AT |
| | LEVEL 4 AND 54 CARLIFTS ARE TO BE INSTALLED AT |
| | LEVEL 5 AT THE ADDRESS OF C F BRICKELL HOTEL LOCATED AT |
| | 8TH STREET IN MIAMI FLORIDA |
| | 4) SEE FAILED SIGNATURE REVIEW |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |