| Notes |
| Date |
Text |
| 2023-06-09 10:08:18 | SIGNATURE REVIEW | | | | | | PREVIOUS COMMENT: | | | 1- ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE | | | REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE | | | TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY | | | FBPE. | | | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU | | | MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED. | | | | | | SEC. 61G15-23.004 F.A.C. . PROCEDURES FOR DIGITALLY | | | SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | RESPONSE: | | | REVISED SIGNATURE NOW HAS THE REQUIRED TEXT BOX BUT | | | THERE ARE TWO THINGS THAT NEED TO BE REVISED: | | | A)THE TEXT BOX LANGUAGE MUST BE IDENTICAL TO THE | | | SAMPLES PUBLISHED BY FBPE. SEE FBPE.ORG/LEGAL/SIGNING-A | | | ND-SEALING-ENGINEERING-DOCUMENTS/ AND REVISE AS | | | REQUIRED TO MATCH. | | | | | | B) THE TEXT BOX LANGUAGE MUST NOT BE A PART OF THE | | | DIGITAL SIGNATURE ITSELF. | | | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU | | | MENTS/ AND REVISE AS REQUIRED TO MATCH. | | | | | | NOTE: | | | THESE COMMENTS WERE VERIFIED WITH THE FBPE | | | INVESTIGATOR. THE TEXT BOX REQUIREMENTS APPLY. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|