| 2022-12-08 19:00:47 | RESIDENTIAL (R2) SECOND BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22090533 |
| | 3650 WHITEHALL DR #404 |
| | |
| | ORIGINAL COMMENT: |
| | 1- WINDOW MULLIONS: |
| | A)1X3 MULLIONS DON'T MEET THE CALCULATED DESIGN |
| | PRESSURES FOR ALL OPENINGS. REVISE AS REQUIRED. SEC. |
| | 1609.1 FBC-BUILDING. |
| | |
| | RESPONSE: |
| | NEW MULLION NOA 19-0405.10 SUBMITTED: |
| | SAME COMMENT APPLIES. 1X3 MULLIONS AND 2X3 MULLIONS |
| | DON'T MEET THE CALCULATED DESIGN PRESSURES. |
| | |
| | ORIGINAL COMMENT: |
| | B)CLEARLY MARK ON THE PRODUCT APPROVAL MULLION |
| | FASTENING. SEC. 1609.1 FBC-BUILDING. |
| | |
| | RESPONSE: |
| | MULLION PRODUCT APPROVAL WAS NOT MARKED SHOWING |
| | FASTENING. |
| | |
| | ORIGINAL COMMENT: |
| | C) CLARIFY SIZE OF CORNER MULLION. FLOOR PLAN SUBMITTED |
| | SPECIFIES 3X3 MULLION, WHILE MULLION PRODUCT APPROVAL |
| | IS MARKED WITH A 4X4 MULLION. REVISE AS REQUIRED TO |
| | MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | NEW MULLION NOA 19-0405.10 SUBMITTED: |
| | 2X3 MULLIONS DON'T MEET THE CALCULATED DESIGN |
| | PRESSURES. |
| | |
| | ORIGINAL COMMENT: |
| | D)MULLION FLORIDA PRODUCT APPROVAL FL34545 STATES IN |
| | ALL SHEETS THAT "THESE MULLIONS CAN ONLY BE USED WITH |
| | 'MARVIN' GLAZING PRODUCTS". NEED TO PROVIDE GLAZING |
| | PRODUCTS TO USE WITH THESE MULLIONS OR PROVIDE ANOTHER |
| | MULLION PRODUCT APPROVAL. |
| | FAC 61G20.3.001. |
| | |
| | RESPONSE: |
| | NEW MULLION NOA 19-0405.10 SUBMITTED. THIS ONE IS OK, |
| | BUT SIZE OF MULLIONS SPECIFIED ON THE FLOOR PLAN |
| | DON???T MEET THE CALCULATED DESIGN PRESSURES. |
| | |
| | ORIGINAL COMMENT: |
| | 2- WINDOW OPENING CONTROL DEVICES: WINDOW OPENING |
| | CONTROL DEVICES ARE REQUIRED WHEN THE WINDOW SILL OF AN |
| | OPERABLE WINDOW IS AT A HEIGHT LESS THAN 36 INCHES |
| | ABOVE THE FINISHED FLOOR. |
| | WINDOW OPENING CONTROL DEVICES NEED TO COMPLY WITH ASTM |
| | F2090. |
| | CLEARLY SPECIFY IF THERE ARE ANY WINDOWS WHERE THE |
| | WINDOW SILL IS LESS THAN 36" ABOVE THE FINISH FLOOR. |
| | SEE SEC. 702.4 FBC-EXISTING BUILDING CODE. |
| | |
| | RESPONSE: |
| | THIS WILL BE VERIFIED IN THE FIELD BY THE BUILDING |
| | INSPECTOR. THIS COMMENT IS JUST TO GIVE HEADS UP ABOUT |
| | THIS REQUIREMENT. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |