| Plan Review Notes For Permit 22090519 |
| Permit Number |
22090519 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-09-30 12:01:00 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 22090519 | | | 9/30/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS 1-5: PLEASE NOTE THE PLUMBING PLANS CANNOT BE | | | APPROVED UNTIL DIGITALLY SIGNED AND SEALED PLANS ARE | | | RESUBMITTED. PLEASE SEE THE FAILED SIGNATURE REVIEW | | | COMMENT- SEC. 107.2.1 WPB. | | | | | | 2) SHEET A.05 OR A.06: PROVIDE COMPLETE ANCHORING | | | DETAILS FOR THE POOL EQUIPMENT INCLUDING PAD SPECS AND | | | TYPE, SIZE, LOCATION, AND NUMBER OF ANCHOR BOLTS- | | | SEC.R4501.22 FBC RES. | | | | | | 3) PLEASE NOTE AN RPZ BACKFLOW PREVENTER SHALL BE | | | INSTALLED AT THE METER TO PROTECT THE POTABLE WATER | | | SERVICE- SECS. C, D, & E WPB CROSS CONNECTION MANUAL. | | | THE DEVICE SHALL BE INSTALLED UNDER A SEPARATE. A PVB | | | BACKFLOW DEVICE IS ALSO REQUIRED FOR AUTOFILL | | | INSTALLATIONS- SEC. P2908.3 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|