| Plan Review Notes For Permit 22090504 |
| Permit Number |
22090504 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-09-26 09:34:57 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. | | | | | | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | | APPROVAL FL14826-R6 COVERS MULTIPLE DESIGN PRESSURE | | | RATINGS. PLEASE SELECT CORRECT PLYWOOD SPECIES GROUP, | | | ANCHOR QUANTITY PAGE #1 OF THE INSTALLATION | | | INSTRUCTIONS THAT MEET OR EXCEED THE MINIMUM DESIGN | | | PRESSURE REQUIREMENT FOR ZONE 3 EXPOSURE CATEGORY C | | | AREAS. (-108). ALL APPLICABLE DETAILS AND ATTACHMENTS | | | MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL | | | DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY | | | COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC | | | ENGINEERING | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | |
|