| 2022-11-14 11:42:30 | CHRIS TROOP HAS COMPLETED THE PEER REVIEW | | | E MAIL COMMENTS | | | | | | ROGER, I HAVE COMPLETED MY REVIEW OF THE FINISHED | | | CONSTRUCTION EC FOR THE SUBJECT SUBMITTAL. I HAVE TWO | | | COMMENTS. | | | 1. THE ICC-ES REPORT FOR THE SMART VENTS SHOULD NOT BE | | | ATTACHED TO THE EC. IT SHOULD BE UPLOADED AS A SEPARATE | | | FILE. I RECOMMEND HAVING THEM RE-SUBMIT THE EC AND | | | ICC-ES REPORT SEPARATELY. | | | 2. SAMANTHA HAS TOLD ME NOT TO PLACE MY BLDG. REVIEW | | | STAMP ON THE EC. FEMA WANTS A CLEAN EC. (THIS WOULD BE | | | AN EASY FIX IF YOU CONCUR, BUT YOU ARE THE ONLY ONE WHO | | | CAN REMOVE YOUR STAMP). IF YOU REQUIRE #1 ABOVE, #2 | | | WOULD NOT BE APPLICABLE. | | | | | | REGARDS, | | | |
|