| 2023-01-30 14:20:37 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22090368 |
| | 1/30/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A-2: THE SANITARY ISOMETRIC DRAWING WAS |
| | REMOVED FROM THE RESUBMITTED PLAN. PLEASE SUBMIT A |
| | REVISED DRAWING - SEC. 107.2.1 & 107.3.5.1.3 WPB. |
| | PLEASE NOTE THE FOLLOWING 1ST REVIEW COMMENTS |
| | CONCERNING THE ISO: |
| | A) THE KITCHENETTE SINK DRAIN SHALL DISCHARGE |
| | DOWNSTREAM OF THE BATHROOM HORIZONTAL WET VENT, AND |
| | SHALL BE SEPARATELY VENTED PER SECS. 912.1 & 912.1.1 |
| | FBC P. |
| | B) THE VENT SYSTEM SERVING EACH BUILDING DRAIN SHALL |
| | HAVE NOT LESS THAN ONE VENT PIPE THAT EXTENDS TO THE |
| | OUTDOORS- SEC. 904.1 FBC P. |
| | C) THE PREVIOUS ISOMETRIC DID NOT INCLUDE THE DRAINAGE |
| | AND VENTING FOR THE DRINKING FOUNTAINS. |
| | |
| | 2) A-2 & A-3: THE LAVATORY AND TOILET CONFIGURATION IN |
| | THE DETAIL ON A-3 DOES NOT MATCH THE CONFIGURATION |
| | SHOWN ON THE FLOOR PLAN ??? SEC. 107.2.1 WPB AND SECS. |
| | 603.3 & 606.2 FBC ACC. |
| | |
| | 3) A-3, DETAIL D-2: PLEASE SHOW THE KNEE AND TOE |
| | CLEARANCES FOR THE LAVATORY AS SHOWN IN FIGURES 306.2 & |
| | 306.3 FBC ACC. MISSING FROM THE DETAIL ARE THE MINIMUM |
| | AND MAXIMUM 17-25 INCHES TOE CLEARANCES UNDER THE LAV, |
| | AND THE 8-INCH MINIMUM KNEE CLEARANCE. |
| | |
| | 4) A-3: SHOW THE HEIGHT OF THE MIRROR FROM THE FINISHED |
| | FLOOR TO THE REFLECTIVE SURFACE- SEC. 603.3. |
| | |
| | 5) A-3: PLEASE SHOW THE HEIGHTS OF THE GRAB BARS |
| | MEASURED TO THE TOPS OF THE GRIPPING SURFACES- SEC. |
| | 609.4 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |