2022-11-15 14:58:48RESIDENTIAL(R3) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22090357
 8795 GIBSON CAY
  
 ORIGINAL COMMENT:
 1- OPENINGS #1, #5, #6 AND #9 ARE IN THE END ZONE NOT
 INTERIOR ZONE. REVISE DESIGN PRESSURES CALCULATIONS AND
 SHUTTERS INSTALLATION SCHEDULE ACCORDINGLY.
 SEC. R301.2.1 FBC-RESIDENTIAL. FIGURE R301.2(7)
 FBC-RESIDENTIAL.
  
 RESPONSE:
 NEED TO REVISE SHUTTERS INSTALLATION SCHEDULE. SPACING
 OF ANCHOR AT THE BOTTOM OF OPENINGS #5, #6 AND #9
 DOESN'T COMPLY WITH THE SPACING REQUIRED FOR THE
 REVISED DESIGN PRESSURES.
 NOTE: OPENINGS #1 AND #8 ARE MISSING THE SPACING FOR
 ANCHOR AT THE BOTTOM OF OPENING.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,