Plan Review Notes
Plan Review Notes For Permit 22090304
Permit Number 22090304
Review Stop P
Sequence Number 1
Notes
Date Text
2022-12-15 15:04:221ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22090304
 12/15/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 POOL PLAN PLUMBING AUDIT.
  
 1) PLEASE NOTE THE PLUMBING FOR THE FOLLOWING ITEMS
 SHOWN ON THE PLANS WERE NOT INCLUDED IN THE AUDIT.
 A) POOL BATHROOM FIXTURES.
 B) DRINKING FOUNTAIN.
 C) POOL SHOWER.
 D) HOSE BIBS FOR DECK AND BATHROOMS.
 E) FLOOR DRAIN, AND POTABLE WATER FILL LINE TO THE
 COLLECTOR TANK IN THE EQUIPMENT ROOM.
  
 2) CONCERNING THE POOL WASTEWATER DISPOSAL NOTES ON
 SHEETS 1-4 PLEASE BE ADVISED OF THE CITY OF WPB
 GUIDELINES FOR POOL WASTEWATER DISPOSAL.
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER???S
 SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH TO
 KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE ALLOWED
 TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE
 CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 3) SHEETS 1 & 2: SPECIFICATIONS FOR AN ACCESSIBLE POOL
 LIFT HAVE BEEN SUBMITTED HOWEVER THE LOCATION OF THE
 LIFT IS NOT SHOWN ON THE DRAWINGS. PLEASE REFER TO
 SECS. 242.2 & 1009.2.1 FBC ACC AND SHOW THE LOCATION ON
 THE PLANS.
  
 4) SHEETS 2 & 4: SHEET 2 SHOWS DIRECT SUCTION LINE FOR
 THE SKIMMER TO THE PUMP BUT NOTE A EQUIPMENT ROOM
 DETAIL ON SHEET 4 SHOWS SKIMMER SUCTION LINE FROM THE
 COLLECTOR TANK. PLEASE CORRECT THE DETAIL OR PROVIDE A
 POOL RECIRCULATION DIAGRAM TO CLARIFY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  