| Notes |
| Date |
Text |
| 2022-10-04 13:41:09 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS NO INDICATION SHOWING THE LOCATION OF THE | | | DIESEL TANK FILL PORT. | | | | | | PER NFPA 1 CH 42 | | | | | | 42.7.2.2 TANK FILLING AND BULK DELIVERY. | | | 42.7.2.2.1 DELIVERY OPERATIONS SHALL MEET ALL | | | APPLICABLE RE QUIREMENTS OF NFPA 385 AND THE | | | REQUIREMENTS OF 42.7.2.2.3 | | | THROUGH 42.7.2.2.46. [30A:9.2.2.1] | | | 42.7.2.2.3 THE DELIVERY VEHICLE SHALL BE SEPARATED FROM | | | ANY | | | ABOVEGROUND TANK IN ACCORDANCE WITH TABLE42.7.2.2.3. | | | | | | 42.7.2.2.3.1 SEPARATION DISTANCES SHALL BE SEPARATED BY | | | THE USE OF CURBING, GUARD POSTS, OR OTHER APPROVED | | | METHODS. | | | | | | PLEASE REIVEW AND PROVIDE DETAILS IN COMPLIANCE WITH | | | THE ABOVE CODES AS WELL AS OTHER APPLICABLE CODES OF CH | | | 42. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|