Date Text
2022-10-04 13:41:09THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION SHOWING THE LOCATION OF THE
 DIESEL TANK FILL PORT.
  
 PER NFPA 1 CH 42
  
 42.7.2.2 TANK FILLING AND BULK DELIVERY.
 42.7.2.2.1 DELIVERY OPERATIONS SHALL MEET ALL
 APPLICABLE RE QUIREMENTS OF NFPA 385 AND THE
 REQUIREMENTS OF 42.7.2.2.3
 THROUGH 42.7.2.2.46. [30A:9.2.2.1]
 42.7.2.2.3 THE DELIVERY VEHICLE SHALL BE SEPARATED FROM
 ANY
 ABOVEGROUND TANK IN ACCORDANCE WITH TABLE42.7.2.2.3.
  
 42.7.2.2.3.1 SEPARATION DISTANCES SHALL BE SEPARATED BY
 THE USE OF CURBING, GUARD POSTS, OR OTHER APPROVED
 METHODS.
  
 PLEASE REIVEW AND PROVIDE DETAILS IN COMPLIANCE WITH
 THE ABOVE CODES AS WELL AS OTHER APPLICABLE CODES OF CH
 42.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  