Plan Review Notes
Plan Review Notes For Permit 22090286
Permit Number 22090286
Review Stop P
Sequence Number 1
Notes
Date Text
2022-09-30 09:05:181ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22090286
 9/30/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS 1-5: PLEASE NOTE THE PLUMBING PLANS CANNOT BE
 APPROVED UNTIL DIGITALLY SIGNED AND SEALED PLANS ARE
 RESUBMITTED. PLEASE SEE THE FAILED SIGNATURE REVIEW
 COMMENT- SEC. 107.2.1 WPB.
  
 2) SHEET 1 OR 2: PROVIDE THE PUMP CURVE ON THE SHEET
 MARKED UP TO SHOW THE TDH AND FLOW RATE OF THE SYSTEM-
 SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & R4501.7.2 &
 R4501.7.3 FBC RES.
  
 3) SHEET 2: UPDATE THE REFERENCED STANDARDS IN THE
 NOTES TO INCLUDE THE ANSI/APSP/ICC3; ANSI/APSP/ICC 4;
 ANSI/APSP/ICC 5; ANSI/APSP/ICC 6; AND ANSI/APSP/ICC 7.
  
 4) PLEASE NOTE THAT THE GAS HEATER SHALL BE INSTALLED
 UNDER A SEPARATE PERMIT- SECS. 105.1, 107.2.1,
 107.3.5.3 WPB.
  
 5) PLEASE NOTE AN RPZ BACKFLOW PREVENTER SHALL BE
 INSTALLED AT THE METER TO PROTECT THE POTABLE WATER
 SERVICE- SECS. C, D, & E WPB CROSS CONNECTION MANUAL.
 THE DEVICE SHALL BE INSTALLED UNDER A SEPARATE. A PVB
 BACKFLOW DEVICE IS ALSO REQUIRED FOR AUTOFILL
 INSTALLATIONS- SEC. P2908.3 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  