| 2022-09-30 09:05:18 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 22090286 |
| | 9/30/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS 1-5: PLEASE NOTE THE PLUMBING PLANS CANNOT BE |
| | APPROVED UNTIL DIGITALLY SIGNED AND SEALED PLANS ARE |
| | RESUBMITTED. PLEASE SEE THE FAILED SIGNATURE REVIEW |
| | COMMENT- SEC. 107.2.1 WPB. |
| | |
| | 2) SHEET 1 OR 2: PROVIDE THE PUMP CURVE ON THE SHEET |
| | MARKED UP TO SHOW THE TDH AND FLOW RATE OF THE SYSTEM- |
| | SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & R4501.7.2 & |
| | R4501.7.3 FBC RES. |
| | |
| | 3) SHEET 2: UPDATE THE REFERENCED STANDARDS IN THE |
| | NOTES TO INCLUDE THE ANSI/APSP/ICC3; ANSI/APSP/ICC 4; |
| | ANSI/APSP/ICC 5; ANSI/APSP/ICC 6; AND ANSI/APSP/ICC 7. |
| | |
| | 4) PLEASE NOTE THAT THE GAS HEATER SHALL BE INSTALLED |
| | UNDER A SEPARATE PERMIT- SECS. 105.1, 107.2.1, |
| | 107.3.5.3 WPB. |
| | |
| | 5) PLEASE NOTE AN RPZ BACKFLOW PREVENTER SHALL BE |
| | INSTALLED AT THE METER TO PROTECT THE POTABLE WATER |
| | SERVICE- SECS. C, D, & E WPB CROSS CONNECTION MANUAL. |
| | THE DEVICE SHALL BE INSTALLED UNDER A SEPARATE. A PVB |
| | BACKFLOW DEVICE IS ALSO REQUIRED FOR AUTOFILL |
| | INSTALLATIONS- SEC. P2908.3 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |