| 2022-09-30 09:43:38 | THE DRYER DUCT TERMINATION MUST MEET FRC M1502.3.1. IT | | | CANNOT HAVE ANYTHING AFTER THE DAMPER, NO SCREEN. | | | | | | FRC M1502.3.1: EXHAUST DUCT TERMINATIONS SHALL BE | | | EQUIPPED WITH A BACKDRAFT DAMPER. SCREENS SHALL NOT BE | | | INSTALLED AT THE DUCT TERMINATION. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|