| Plan Review Notes For Permit 22090273 |
| Permit Number |
22090273 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-09-26 09:46:52 | PLEASE ADDRESS THE ORIGINAL REVIEW COMMENTS BELOW: | | | | | | 1) PROVIDE THE DUCT SIZES AND THE MATERIAL FOR THE | | | EXHAUST FANS AND THE DRYER EXHAUST. FBC 107.3.5 | | | 2) THE DESIGNER OF THE DRAWINGS MUST INCLUDE THEIR | | | PRINTED NAME AND SIGNATURE ON EACH DRAWING. FBC 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|