| Plan Review Notes For Permit 22090153 |
| Permit Number |
22090153 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-10-03 15:58:20 | MOCK UP WINDOWS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE "VISUAL MOCK-UP SHOP DRAWING" NEEDS TO BE SIGNED | | | AND SEALED BY THE ENGINEER WHO DESIGNED IT. FBC WPB | | | 107.1 | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | | | | 2) ON THE "VISUAL MOCK-UP SHOP DRAWING" PLEASE SHOW THE | | | WIND DESIGN CRITERIA PER FBC 1603.1.4 | | | |
|