2022-11-30 09:06:071ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22090134
 11/30/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED GENERATOR SPECS DO NOT INDICATE THE
 GENERATOR IS UL 2200 LISTED- SEC. 616.1 FBC FG. PLEASE
 PROVIDE ADDITIONAL DOCUMENTATION TO VERIFY COMPLIANCE.
  
 2) SHEET ME1: INDICATE THE BTU LOAD OF THE GENERATOR
 AND INPUT PRESSURE IN THE NOTES OR ON THE PLAN. CLARIFY
 IF A NEW REGULATOR AND A LISTED FLEX LINE WILL BE
 INSTALLED AND PROVIDE THESE DETAILS- TYPE AND SIZE OF
 EXISTING SUPPLY LINE, INPUT AND OUTPUT PRESSURES AT THE
 REGULATOR, TYPE AND SIZE OF FLEX LINE- SECS. 402.1,
 410.2 & 616.2 FBC FG.
  
 3) ME1: REFER TO THE MANUFACTURER'S GUIDELINES AND
 PROVIDE EXHAUST DUCT DETAILS AS RECOMMENDED BY THE
 MANUFACTURER- SEC. 616.1 FBC FG. INDICATE THE TYPE AND
 GAUGE OF METAL EXHAUST DUCT AND DETAIL METHOD OF DUCT
 ATTACHMENT AND SEALING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  