| Plan Review Notes For Permit 22090134 |
| Permit Number |
22090134 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-11-30 09:06:07 | 1ST REVIEW FBC-2020 FUEL GAS | | | PERMIT- 22090134 | | | 11/30/2022 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE SUBMITTED GENERATOR SPECS DO NOT INDICATE THE | | | GENERATOR IS UL 2200 LISTED- SEC. 616.1 FBC FG. PLEASE | | | PROVIDE ADDITIONAL DOCUMENTATION TO VERIFY COMPLIANCE. | | | | | | 2) SHEET ME1: INDICATE THE BTU LOAD OF THE GENERATOR | | | AND INPUT PRESSURE IN THE NOTES OR ON THE PLAN. CLARIFY | | | IF A NEW REGULATOR AND A LISTED FLEX LINE WILL BE | | | INSTALLED AND PROVIDE THESE DETAILS- TYPE AND SIZE OF | | | EXISTING SUPPLY LINE, INPUT AND OUTPUT PRESSURES AT THE | | | REGULATOR, TYPE AND SIZE OF FLEX LINE- SECS. 402.1, | | | 410.2 & 616.2 FBC FG. | | | | | | 3) ME1: REFER TO THE MANUFACTURER'S GUIDELINES AND | | | PROVIDE EXHAUST DUCT DETAILS AS RECOMMENDED BY THE | | | MANUFACTURER- SEC. 616.1 FBC FG. INDICATE THE TYPE AND | | | GAUGE OF METAL EXHAUST DUCT AND DETAIL METHOD OF DUCT | | | ATTACHMENT AND SEALING. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|