| 2022-11-03 14:52:35 | REMODEL - ADDITION ?? |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) BUILDING PERMIT APPLICATION SAYS "INTERIOR |
| | RENOVATION" YET THE PLANS PROVIDED SHOW AN ADDITION - |
| | PLEASE CORRECT THE BUILDING PERMIT APPLICATION "WORK |
| | DESCRIPTION" OR REMOVE THE ADDITION DRAWINGS FROM |
| | PROJECTDOX. |
| | CANNOT APPROVE AN INTERIOR RENOVATION FOR A |
| | NON-EXISTENT BUILDING - THE ADDITION IS SHOWN ON THE |
| | INTERIOR FLOOR PLAN. |
| | |
| | 2) MOST OF THE DRAWINGS PROVIDED HAVE THE STATEMENT |
| | "NOT FOR CONSTRUCTION" CANNOT APPROVE DRAWINGS WITH |
| | THAT NOTE ON THEM - PLEASE REMOVE THE NOTE. |
| | |
| | 3) DRAWINGS SHOW ACCESSIBLE PARKING TO BE REMOVED - |
| | PLEASE SHOW NEW ACCESSIBLE PARKING, ACCESS AISLE AND |
| | ACCESSIBLE PATH TO THE ENTRY FBC A |
| | |
| | 4) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING |
| | INFORMATION FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION |
| | DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT |
| | SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE |
| | THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING |
| | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE |
| | ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED |
| | GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS |
| | APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN |
| | FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE |
| | WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE |
| | SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED |
| | WATER RETAINING SWALES) |
| | |
| | 5) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE ROOFING SYSTEM. FBC WPB |
| | 107.2.1.1 |
| | |
| | 6) PLEASE SHOW THE WALL FINISH SURROUNDING THE TOILET |
| | AND MOP SINK TO COMPLY WITH FBC 1210.2.2 WALLS AND |
| | PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT |
| | CONSIDERED A HARD SURFACE) |
| | |
| | 7) ACCESSIBLE RESTROOM = PLEASE SHOW THE TOILET PAPER |
| | HOLDER DIMENSIONS FROM THE FACE OF THE TOILET PER FBC A |
| | 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| | DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 |
| | INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND |
| | SHALL NOT BE LOCATED BEHIND GRAB BARS |
| | |
| | 8) ACCESSIBLE RESTROOM = PLEASE USE THE WORDS |
| | "REFLECTING SURFACE" WHEN REFERRING TO THE DIMENSION |
| | FROM THE FLOOR TO THE BOTTOM OF THE MIRROR FBC A 603.3 |
| | MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 9) ACCESSIBLE RESTROOM = PLEASE SHOW THE MAXIMUM HEIGHT |
| | OF THE TOILET OR SHOWER GRAB BAR TO THE TOP OF THE |
| | GRIPPING SURFACE NOT TO THE CENTER AS SHOWN ON THE |
| | DRAWING (A-003) - FBC A 609.4 POSITION OF GRAB BARS. |
| | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACE, |
| | |
| | 10) DRAWING A-300 - ACCESSIBLE DETAILS SHOULD BE PER |
| | 2020 FBC ACCESSIBILITY |
| | |
| | 11) PLEASE SHOW THE NEW EXTERIOR DOOR LANDINGS - FBC |
| | 1010.1.5 |
| | |
| | 12) PLEASE SHOW THE NEW FLOOR SLAB THICKNESS - FBC |
| | 1907.1 |
| | |
| | 13) PLEASE SHOW THAT TERMITE PROTECTION IS REQUIRED - |
| | FBC 1816 |
| | |
| | |
| | |