| Plan Review Notes For Permit 22090099 |
| Permit Number |
22090099 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-09-20 11:24:58 | 09/20/22 FAILED - THE PROPOSED SITE WALL DOES NOT MEET | | | THE CORNER VISIBILITY REQUIREMENTS OF SEC305. PER CITY | | | CODE, A VISIBILITY TRIANGLE EXTENDING 20 FT IN EITHER | | | DIRECTION FROM THE CORNER OF THE PROPERTY MUST BE | | | MAINTAINED, THEREFORE THE WALL CANNOT ENROACH INTO THIS | | | TRIANGLE. | | | | | | ALEXANDER FOWLKES | | | [email protected] | | | 5618221431 | | | |
|