2022-10-25 08:21:25ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) THE ROOF HEIGHT IS HIGHER THAN THE MAXIMUM SHOWN ON
 THE TABLES IN RAS 127 - WIND DESIGN PRESSURES PROVIDED
 NEED TO BE SIGNED AND SEALED BY AN ARCHITECT OR
 ENGINEER PER FBC RAS 127 - THIS STANDARD COVERS THE
 PROCEDURE FOR DETERMINING THE MOMENT OF RESISTANCE (MR)
 AND MINIMUM CHARACTERISTIC RESISTANCE LOAD (F') TO
 INSTALL A TILE SYSTEM ON BUILDINGS OF A SPECIFIED ROOF
 SLOPE AND HEIGHT. COMPLIANCE WITH THE REQUIREMENTS AND
 PROCEDURES HEREIN SPECIFIED, WHERE THE DESIGN WIND
 UPLIFT PRESSURES (PASD) HAVE BEEN DETERMINED BASED ON
 TABLES 1-3 OR TABLES 4-6, TABLES 7-9 OR TABLES 10-12 OF
 THIS STANDARD, AS APPLICABLE, DO NOT REQUIRE ADDITIONAL
 SIGNED AND SEALED ENGINEERING DESIGN CALCULATION. ALL
 OTHER CALCULATIONS MUST BE PREPARED, SIGNED AND SEALED
 BY A PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT.
  