Plan Review Notes
Plan Review Notes For Permit 22090042
Permit Number 22090042
Review Stop M
Sequence Number 1
Notes
Date Text
2022-09-08 06:09:371ST REVIEW FMC
 PERMIT: 22090042
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED REVISION FORM STATES THIS REVISION IS
 FOR- COOLING TOWER REVISION, THE EQUIPMENT SUBMITTAL
 AND ENGINEERING DRAWINGS FOR THE STEEL THAT WAS
 INSTALLED. I DO NOT SEE THE EQUIPMENT SPECS OR THE
 ENGINEERED DRAWINGS FOR THE STEEL THAT WAS INSTALLED.
 PROVIDE A COMPLETE SCOPE OF WORK FOR THIS REVISION AND
 SUBMIT ALL DOCUMENTS PERTAINING TO THIS REVISION. IT
 DOES APPEAR THERE ARE NEW PIPES BEING INSTALLED ON THIS
 REVISION? FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  