2022-11-16 09:59:201ST REVIEW FMC
 PERMIT: 22090010
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS. FEC R101.5.1.1.1
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC R403.7.1
  
 3) PROVIDE THE CFM???S OF THE BATH EXHAUST FAN. FRC
 M1507.4
  
 4) PROVIDE THE CFM???S OF THE HOOD EXHAUST FAN AND THE
 TERMINATION LOCATION FOR THE HOOD EXHAUST DUCT. FRC
 M1503.4
  
 5) PLEASE SHOW THE REQUIRED RETURN AIR DUCT WORK FROM
 LIVING SPACE BACK TO THE AHU IN THE MECHANICAL ROOM AND
 STORAGE CLOSET AS RETURN AIR CANNOT BE FROM A
 MECHANICAL ROOMS OR CLOSETS. FRC M1602.2
  
 6) REMOVE THE RETURN AIR GRILLE FROM THE BATHROOM AS
 RETURN AIR CANNOT COME FROM A BATHROOM. FRC M1602.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  