Plan Review Notes
Plan Review Notes For Permit 22081533
Permit Number 22081533
Review Stop M
Sequence Number 1
Notes
Date Text
2022-11-22 15:43:101ST REVIEW FMC
 PERMIT: 22081533
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ADDRESS FOR THIS PERMIT APPLICATION, 4334 N
 FLAGLER DR. DOES NOT HAVE A GENERATOR PERMIT. THE
 GENERATOR ON THE DRAWING HAS NOT HAD A MECHANICAL
 REVIEW. UNTIL A MECHANICAL PERMIT FOR THE GENERATOR AND
 A PLAN REVIEW HAS BEEN COMPLETED AND APPROVED I CANNOT
 REVIEW THE FUEL PIPING FOR EITHER GENERATOR.
  
 2) THE ADDRESS FOR THE NORTH GARAGE, 4444 N FLAGLER DR.
 HAS A PERMIT APPLICATION FOR ONE 600KV GENERATOR WHICH
 HAS THE FOLLOWING PLAN REVIEWS: ADDRESSING, ELECTRICAL,
 FIRE, SIGNATURE AND ZONING. A MECHANICAL PLAN REVIEW
 HAS NOT BEEN SCHEDULED OR COMPLETED FOR EITHER THE
 PERMITTED GENERATOR IN THE NORTH GARAGE OR THE
 UNPERMITTED GENERATOR IN THE SOUTH GARAGE.
  
 3) PLEASE PROVIDE MECHANICAL APPLICATIONS AND PLANS
 FOR THE MECHANICAL REVIEW FOR EACH GENERATOR. THIS
 SUBMITTAL SHOULD INCLUDE SITE PLANS SHOWING THE
 PROPERTY LINES ALONG WITH THE EXHAUST TERMINATION
 LOCATIONS FOR BOTH GENERATORS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  