| Date |
Text |
| 2022-09-15 06:15:54 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 2ND REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | |
| | PERMIT #22081479 BUILDING REVIEW FAILED. 386 PALMETTO |
| | RD. |
| | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL27499.12-R4 COVERS MULTIPLE INSTALLATION |
| | OPTIONS TO MEET DESIGN UPLIFT PRESSURES. PLEASE SELECT |
| | CORRECT INSTALLATION OPTION FROM PAGE #2 OF THE |
| | EVALUATION REPORT THAT MEET OR EXCEED THE MINIMUM |
| | DESIGN PRESSURE REQUIREMENT FOR ZONE 3 EXPOSURE |
| | CATEGORY C AREAS. (-121.). ALL APPLICABLE DETAILS AND |
| | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| | APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| | SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| | SITE-SPECIFIC ENGINEERING |
| | 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL1654-R29 SYSTEM NO. W-111 DOES NOT MEET THE |
| | MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17 |
| | FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT |
| | MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR |
| | EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED |
| | ENGINEERED NAILING CALCULATIONS WITH AN APPROVED |
| | SYSTEM. |
| | 3. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R36 |
| | (HVHZ) IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF |
| | WEST PALM BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT |
| | CONSIDER USING FL5259-R36 (NON-HVHZ). |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX |
| | |
| | JONATHAN N. BROOKS JR. |
| | BUILDING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENTIAL SERVICES |
| | |