2022-09-02 10:28:51FIRE PROVISO COMMENTS:
  
 (1) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL
 PHASES OF DEMOLITION AND CONSTRUCTION.
  
 (2) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A FIRE
 WATCH.
  
 (3) ALL EXISTING LIFE SAFETY SYSTEM SHALL BE PROTECTED
 FROM DAMAGE DURING ALL PHASES OF DEMOLITION AND
 CONSTRUCTION.
  
 (4) ANY CHANGES TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
 (5) ANY WORK INVOLVING A FIRE RATED WALL AND/OR
 PARTITION SHALL ENSURE THE FIRE RATING IS MAINTAINED.
  