Plan Review Notes
Plan Review Notes For Permit 22081442
Permit Number 22081442
Review Stop B
Sequence Number 1
Notes
Date Text
2022-10-21 10:46:26PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE MINIMUM UNIFORM DISTRIBUTED LIVE LOAD
 FOR THE ELEVATED WALKWAY ON THE PLANS. FBC 1607.1
  
 2) SPECIFY THE APPLICABLE BUILDING CODE AND WIND SPEED
 DATA ON THE PLANS. FBC 1609
  
 3) SHOW THAT THE STAIR AND RAMP COMPONENTS COMPLY WITH
 FBC ACCESSIBILITY.
 - 405 RAMPS
 - 405.6 RISE. THE RISE FOR ANY RAMP RUN SHALL BE 30
 INCHES (760 MM) MAXIMUM.
 - 405.8 HANDRAILS. RAMP RUNS WITH A RISE GREATER THAN 6
 INCHES (150 MM) SHALL HAVE HANDRAILS COMPLYING WITH
 505.
 - 405.9 EDGE PROTECTION. EDGE PROTECTION COMPLYING WITH
 405.9.1 OR 405.9.2 SHALL BE PROVIDED ON EACH SIDE OF
 RAMP RUNS AND AT EACH SIDE OF RAMP LANDINGS
  
 - 505.1 GENERAL HANDRAILS PROVIDED ALONG WALKING
 SURFACES COMPLYING WITH 403, REQUIRED AT RAMPS
 COMPLYING WITH 405, AND REQUIRED AT STAIRS COMPLYING
 WITH 504 SHALL COMPLY WITH 505.
 ADVISORY 505.1 GENERAL. HANDRAILS ARE REQUIRED ON RAMP
 RUNS WITH A RISE GREATER THAN 6 INCHES (150 MM) (SEE
 405.8) AND ON CERTAIN STAIRWAYS (SEE 504). HANDRAILS
 ARE NOT REQUIRED ON WALKING SURFACES WITH RUNNING
 SLOPES LESS THAN 1:20. HOWEVER, HANDRAILS ARE REQUIRED
 TO COMPLY WITH 505 WHEN THEY ARE PROVIDED ON WALKING
 SURFACES WITH RUNNING SLOPES LESS THAN 1:20 (SEE
 403.6). SECTIONS 505.2, 505.3, AND 505.10 DO NOT APPLY
 TO HANDRAILS PROVIDED ON WALKING SURFACES WITH RUNNING
 SLOPES LESS THAN 1:20 AS THESE SECTIONS ONLY REFERENCE
 REQUIREMENTS FOR RAMPS AND STAIRS