| Date |
Text |
| 2022-12-21 10:10:15 | THE PREVIOUS COMMENTS BY FIRE HAVE NOT BEEN ADDRESSED. |
| | |
| | THE NEW SUBMITTED DOCUMENTS DATED 12/19/22 WITHIN THE |
| | TITLE BLOCK INDICATE AN ADDRESS OF 7640 OKEECHOBEE |
| | BLVD. |
| | |
| | WHEREAS THE ORIGINAL SUBMITTED DOCUMENTS AND |
| | APPLICATION INDICATED 477 S ROSEMARY AVE # 187. |
| | |
| | PLEASE REIVEW AND CORRECT WITH THE PROPER ADDRESS AND |
| | APPLICABLE DOCUMENTS TO ADDRESS FIRE'S PREVIOUS |
| | COMMENTS WHICH ARE NOTED BELOW. |
| | |
| | ******************************************************* |
| | ******************************************************* |
| | **************************************************** |
| | |
| | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS NO INDICATION OF THE GENERATOR TYPE, |
| | MANUFACTURES SPEC SHEET, FUEL SUPPLY, NOR EXHAUST |
| | LOCATION FOR THE PROPOSED GENERATOR REPLACEMENT. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | PER NFPA 110 |
| | |
| | CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY |
| | SYSTEMS (EPSSS) |
| | 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF |
| | ELECTRICAL |
| | POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO |
| | LOADS FOR |
| | A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND |
| | WITHIN A SPECI FIED TIME FOLLOWING LOSS OR FAILURE OF |
| | THE NORMAL POWER SUPPLY |
| | AS SPECIFIED IN TABLE 4.1(B). |
| | |
| | 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN |
| | HOURS, FOR |
| | WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD |
| | WITHOUT |
| | BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).] |
| | 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN |
| | SECONDS, |
| | THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE |
| | TRANSFER |
| | SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE |
| | 4.1(B) |
| | PROVIDES THE TYPES DEFINED BY THIS STANDARD. |
| | 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF |
| | EQUIPMENT |
| | INSTALLATION, PERFORMANCE, AND MAINTENANCE. |
| | 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE |
| | OF THE |
| | EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE |
| | OR |
| | SERIOUS INJURIES. |
| | 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE |
| | OF TH |
| | |
| | PLEASE PROVIDE |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |