| 2023-01-12 09:45:15 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 22081426 |
| | 1/12/23 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE A GAS RISER DRAWING IN COMPLIANCE WITH SEC. |
| | 107.3.5.1.3 WPB. THE RISER SHALL INCLUDE THE FOLLOWING |
| | INFORMATION AS REQUIRED BY SEC. 402 FBC FG. |
| | |
| | A) TYPE OF GAS- NATURAL OR LP. (PLEASE NOTE SEPARATE |
| | PERMITS ARE REQUIRED FOR LP TANKS). |
| | B) DELIVERY PRESSURE AT THE METER. |
| | C) TOTAL BTU LOAD OF THE GENERATOR AND ALL EXISTING |
| | APPLIANCE BTU LOADS. |
| | D) TYPES AND SIZES OF PIPING. |
| | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES. |
| | H) OUTLET PRESSURES AT REGULATORS. |
| | I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | K) PIPE SIZING TABLES. |
| | |
| | 2) SHOW THE TYPE AND SIZE OF CONNECTOR FROM THE |
| | SHUTOFF/REGULATOR ASSEMBLY TO THE GENERATOR. PLEASE |
| | NOTE THE GENERATOR SHALL NOT BE RIGIDLY CONNECTED TO |
| | THE GAS SUPPLY- SECS. 411.1.5 & 616.2 FBC FG. |
| | A) PLEASE NOTE THE SUBMITTED MANUFACTURER' S |
| | SPECIFICATIONS FOR THE GENERATOR RECOMMENDS THE |
| | REGULATOR TO BE LOCATED A MINIMUM 10 FT. FROM THE |
| | GENERATOR SET CONNECTION POINT- SEE PAGE 2 OF THE |
| | GENERAC DESIGN GUIDE WHICH ALSO PROVIDES REGULATOR |
| | SELECTION SPECIFICATIONS- SEC. 410.2 FBC FG. |
| | |
| | 3) PROVIDE A DIMENSIONED SITE PLAN WITH ENLARGED |
| | DRAWING OF THE GENERATOR SHOWING THE FOLLOWING |
| | INFORMATION. |
| | A) GAS PIPING RUNS ON THE EXTERIOR AND INTERIOR THE |
| | BUILDING AND MEANS OF PROTECTING PIPING FROM PHYSICAL |
| | DAMAGE AND CORROSION- SEC. 404. |
| | B) PROTECTION FROM VEHICLE IMPACT FOR THE GENERATOR AND |
| | APPURTENANCES- SEC. 303.4. |
| | |
| | 4) PROVIDE A VENTING PLAN FOR THE GENERATOR EXHAUST |
| | LISTING THE CATEGORY OF THE VENT SYSTEM- 1,2,3, OR 4, |
| | AND VENT SPECIFICARTIONS- TYPES ANSD SIZE, VENT RUN AND |
| | TERNINATION LOCATION WITH CLEARANCE DISTANCES TO |
| | MECHANICAL AND GRAVITY AIR INTALES INTO THE BUILDING- |
| | SEC. 503.1 FBC FG. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |