| Plan Review Notes For Permit 22081426 |
| Permit Number |
22081426 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-03-16 16:56:12 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PROVIDE DETAILS FOR THE GENERATOR PAD AND SPECIFY | | | HOW THE GENERATOR WILL BE ANCHORED TO THE PAD TO RESIST | | | WIND LOADS. FBC 107.2.1 AND CHAPTER 16 | | | | | | 2) SPECIFY THE WIND LOAD DESIGN DATA ON THE DRAWINGS. | | | FBC CHAPTER 16 | | | | | | 3) DRAWINGS AND DETAILS ARE REQUIRED TO BE SIGNED AND | | | SEALED BY THE DESIGN PROFESSIONAL. FS471 |
|