2022-10-17 11:19:49THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO SPECIFIC INDICATION OF WHERE THE FENCE
 WILL BE LOCATED ON THE SITE PLAN.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THEPROPOSED
 LOCATION OF THE FENCE.
  
  
 1A) THERE ARE NO LOCATIONS OF ANY GATE ACCESS POINTS OR
 GATE WIDTHS.
  
 PLEASE PROVIDE GATE LOCATIONS AND WIDTH DETAIL THAT
 WILL PROVIDE FOR FD EMERGENCY ACCESS.
  
  
 1B) IT IS RECOMMENDED, NOT REQUIRED, FOR THE GATES BE
 PROVIDED WITH KNOX PADLOCKS.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  