| 2022-10-12 08:36:32 | 4TH NFIP PLAN REVIEW |
| | |
| | CHRISTOPHER S. THROOP, CBO, BU, BN, PX, CFM |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | CITY ORDINANCE NO. 4658-16 AND NO. 4729-17 |
| | FEMA DESK REFERENCE P 758 |
| | FBC R322 FLOOD-RESISTANT CONSTRUCTION |
| | FEMA TECH BULLETIN #1 |
| | |
| | FINISHED CONSTRUCTION ELEVATION CERTIFICATE |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. SECTION A9 (C) STATES "TOTAL NET AREA OF FLOOD |
| | OPENINGS IS 2000 SQ. IN." |
| | NOTE: (IF FLOOD VENT MODEL 1540-520 IS 8.25"X16.25", |
| | THEN EACH VENT CAN ONLY BE 134 SQ. IN.'S FOR A MAX OF |
| | 1340 SQ. IN.'S.) |
| | |
| | NET AREA OF ENGINEERED FLOOD VENTS SHALL BE CALCULATED |
| | BY A DESIGN PROFESSIONAL PER FEMA TECH. BULLETIN #1, |
| | PAGE 34, FIGURE 25. |
| | |
| | 2. COMMENT IN SECTION D STATES "SMART VENT MODEL |
| | 1540-520 ARE RATED FOR 200 SQ. IN. PER UNIT". (THIS |
| | SHOULD STATE 200 SQ. FT. PER UNIT). PLEASE CORRECT. |
| | |
| | 3. COMMENT IN SECTION D STATES SECTION C2E: A/C PAD AT |
| | SOUTHSIDE=8.96. |
| | EQUIPMENT SERVICING THE BUILDING SHALL BE AT OR ABOVE |
| | THE DESIGN FLOOD ELEVATION (DFE) OF 9'0"NAVD. PLEASE |
| | CORRECT. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |