| 2022-09-02 13:47:17 | FIRE PROVISO COMMENTS: | | | | | | (1) MANUAL FIRE ALARM BOXES SHALL BE LOCATED WITHIN 5? | | | OF EACH EXIT DOORWAY. | | | | | | MANUAL FIRE ALARM BOXES SHALL BE CONSPICUOUS AND | | | UNOBSTRUCTED. | | | | | | NFPA 72, 17.14 | | | | | | (2) THE FIRE ALARM SYSTEM SHALL PASS 24- HOUR BATTERY | | | TESTING COMPLIANT WITH NFPA 72 14.4.3.2 | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|