2022-09-02 13:47:17FIRE PROVISO COMMENTS:
  
 (1) MANUAL FIRE ALARM BOXES SHALL BE LOCATED WITHIN 5?
 OF EACH EXIT DOORWAY.
  
 MANUAL FIRE ALARM BOXES SHALL BE CONSPICUOUS AND
 UNOBSTRUCTED.
  
 NFPA 72, 17.14
  
 (2) THE FIRE ALARM SYSTEM SHALL PASS 24- HOUR BATTERY
 TESTING COMPLIANT WITH NFPA 72 14.4.3.2
  