| Notes |
| Date |
Text |
| 2022-11-29 10:34:54 | THE MECHANICAL EQUIPMENT SIZING CALCULATIONS SHOULD | | | SHOW THE ENTRE HOUSE PLUS THE NEW ADDITION TO SHOW THAT | | | THE EXISTING EQUIPMENT IS SIZED TO CONDITION THE | | | EXISTING SPACE AND THE NEW ADDITION. THE EQUIPMENT | | | SIZING CALCULATIONS SUBMITTED ARE FOR 243 SQ. FT. | | | PLEASE PROVIDE THE CALCULATIONS FOR THE EXISTING PLUS | | | ALL OF THE ADDITION. FBC 107.3.5 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|