| 2022-10-17 17:09:23 | PLEASE ADDRESS THE 2ND REVIEW CYCLE COMMETS BELOW: | | | | | | 1) THE MECHANICAL SYSTEM DESIGN FOR THE COTTAGE MUST | | | MEET THE SEPARATION REQUIREMENTS FROM THE GARAGE. FRC | | | R302.5 | | | | | | 2) SHOW THE DUCTED RETURN BACK TO THE AHU IN THE | | | GARAGE. RETURN AIR CANNOT BE TAKEN FROM A GARAGE. FRC | | | M1602 NUMBER 4 | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|