2022-10-17 17:09:23PLEASE ADDRESS THE 2ND REVIEW CYCLE COMMETS BELOW:
  
 1) THE MECHANICAL SYSTEM DESIGN FOR THE COTTAGE MUST
 MEET THE SEPARATION REQUIREMENTS FROM THE GARAGE. FRC
 R302.5
  
 2) SHOW THE DUCTED RETURN BACK TO THE AHU IN THE
 GARAGE. RETURN AIR CANNOT BE TAKEN FROM A GARAGE. FRC
 M1602 NUMBER 4
  
  