Plan Review Notes
Plan Review Notes For Permit 22081317
Permit Number 22081317
Review Stop G
Sequence Number 2
Notes
Date Text
2022-10-12 15:09:112ND GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 THE CURRENT DOCUMENTS WERE SUBMITTED BEFORE THE
 PLUMBING REVIEW, AND NO NEW PAGES HAVE BEEN SUBMITTED
 SINCE THE FAILED REVIEW.
  
 1)----NO CHANGES SINCE 1ST REVIEW---- SHEETS P-1, P-2,
 P-3: THE PLANS INDICATE THE EXISTING GARAGE AND
 ATTACHED SEMI-FINISHED BASE AREA WILL BE REMODELED AND
 CONVERTED INTO A DWELLING UNIT. A SEPARATE PERMIT WILL
 REQUIRED FOR THE PROPOSED WORK- SECS. 105.1& 107.2.1
 WPB.
  
 2) ----NO CHANGES SINCE 1ST REVIEW----P-1: THE DRAWINGS
 ARE LABELED AS WATER/GAS HOWEVER NO GAS PIPING OR GAS
 APPLIANCES ARE SHOWN ON THE PLANS. PLEASE PROVIDE A GAS
 RISER DRAWING AND GAS APPLIANCE LOCATION PLAN- SEC.
 107.3.5.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  