| 2022-10-12 15:09:11 | 2ND GAS REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | THE CURRENT DOCUMENTS WERE SUBMITTED BEFORE THE |
| | PLUMBING REVIEW, AND NO NEW PAGES HAVE BEEN SUBMITTED |
| | SINCE THE FAILED REVIEW. |
| | |
| | 1)----NO CHANGES SINCE 1ST REVIEW---- SHEETS P-1, P-2, |
| | P-3: THE PLANS INDICATE THE EXISTING GARAGE AND |
| | ATTACHED SEMI-FINISHED BASE AREA WILL BE REMODELED AND |
| | CONVERTED INTO A DWELLING UNIT. A SEPARATE PERMIT WILL |
| | REQUIRED FOR THE PROPOSED WORK- SECS. 105.1& 107.2.1 |
| | WPB. |
| | |
| | 2) ----NO CHANGES SINCE 1ST REVIEW----P-1: THE DRAWINGS |
| | ARE LABELED AS WATER/GAS HOWEVER NO GAS PIPING OR GAS |
| | APPLIANCES ARE SHOWN ON THE PLANS. PLEASE PROVIDE A GAS |
| | RISER DRAWING AND GAS APPLIANCE LOCATION PLAN- SEC. |
| | 107.3.5.3 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |