| 2022-08-31 12:53:32 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 22081317 |
| | 8/31/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P-1, P-2, P-3: THE PLANS INDICATE THE |
| | EXISTING GARAGE AND ATTACHED SEMI-FINISHED BASE AREA |
| | WILL BE REMODELED AND CONVERTED INTO A DWELLING UNIT. A |
| | SEPARATE PERMIT WILL REQUIRED FOR THE PROPOSED WORK- |
| | SECS. 105.1& 107.2.1 WPB. |
| | |
| | 2) P1, P2, & P3: TWO DWELLINGS ON THE SAME LOT WILL |
| | REQUIRE WATER USERS TO INSTALL A BACKFLOW PREVENTION |
| | ASSEMBLY AT THE POINT OF DELIVERY. A REDUCED PRESSURE |
| | ZONE BACKFLOW DEVICE WILL BE REQUIRED FOR THE WATER |
| | METER PER THE CITY OF WEST PALM CROSS UTILITIES |
| | DEPARTMENT AND THEIR CONNECTION CONTROL PROGRAM. |
| | PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR |
| | SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE |
| | BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB |
| | AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| | BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| | |
| | 3) P1: THE LOCATION OF THE TANKLESS WATER HEATER IN THE |
| | LAUNDRY CLOSET IS NOT IN COMPLIANCE WITH SECS. P2801.4 |
| | & M1305.1 FBC RES- A 30X30 INCH WORKING SPACE IS |
| | REQUIRED ON THE CONTROL SIDE OF THE UNIT WITHOUT |
| | REMOVAL OF THE STACKABLE WASHER/DRYER APPLIANCE. |
| | |
| | 4) P-1: THE WATER PIPE LEGEND NOTE #3 SPECIFYING A |
| | 1/2-INCH MAIN HW LINE APPEARS TO BE INCORRECT AND |
| | SHOULD INDICATE 3/4-INCH FOR THE WSFU DEMAND- P2903.6 & |
| | P2903.7 FBC RES. |
| | |
| | 5) P-1, P-2: THE DRAWINGS SHOW A WATER LINE TO A BBQ |
| | SINK BUT NO DRAIN AND VENT PIPING- SEC. P2601.2 FBC |
| | RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |