2022-08-31 12:53:321ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22081317
 8/31/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P-1, P-2, P-3: THE PLANS INDICATE THE
 EXISTING GARAGE AND ATTACHED SEMI-FINISHED BASE AREA
 WILL BE REMODELED AND CONVERTED INTO A DWELLING UNIT. A
 SEPARATE PERMIT WILL REQUIRED FOR THE PROPOSED WORK-
 SECS. 105.1& 107.2.1 WPB.
  
 2) P1, P2, & P3: TWO DWELLINGS ON THE SAME LOT WILL
 REQUIRE WATER USERS TO INSTALL A BACKFLOW PREVENTION
 ASSEMBLY AT THE POINT OF DELIVERY. A REDUCED PRESSURE
 ZONE BACKFLOW DEVICE WILL BE REQUIRED FOR THE WATER
 METER PER THE CITY OF WEST PALM CROSS UTILITIES
 DEPARTMENT AND THEIR CONNECTION CONTROL PROGRAM.
 PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 3) P1: THE LOCATION OF THE TANKLESS WATER HEATER IN THE
 LAUNDRY CLOSET IS NOT IN COMPLIANCE WITH SECS. P2801.4
 & M1305.1 FBC RES- A 30X30 INCH WORKING SPACE IS
 REQUIRED ON THE CONTROL SIDE OF THE UNIT WITHOUT
 REMOVAL OF THE STACKABLE WASHER/DRYER APPLIANCE.
  
 4) P-1: THE WATER PIPE LEGEND NOTE #3 SPECIFYING A
 1/2-INCH MAIN HW LINE APPEARS TO BE INCORRECT AND
 SHOULD INDICATE 3/4-INCH FOR THE WSFU DEMAND- P2903.6 &
 P2903.7 FBC RES.
  
 5) P-1, P-2: THE DRAWINGS SHOW A WATER LINE TO A BBQ
 SINK BUT NO DRAIN AND VENT PIPING- SEC. P2601.2 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  