| 2022-09-19 15:15:08 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | GAS COMMENTS: DENIED |
| | |
| | PER WPB FBC 107.2.1, 107.3.5.1.5, FBC FG 305.1 AND FBC |
| | RES G2408.1, MANUFACTURER'S SPECIFICATION/INSTALLATION |
| | MANUAL(S) FOR ALL GAS EQUIPMENT SHALL BE ON SITE AT THE |
| | TIME OF INSPECTION. |
| | |
| | CITY OF WEST PALM BEACH GAS PIPING AFFIDAVIT OR |
| | MANOMETER TEST DOCUMENT REQUIRED AT JOBSITE FOR FINAL |
| | GAS INSPECTION. CALL 561-805-6692 FOR ADDITIONAL |
| | INFORMATION |
| | |
| | |
| | A. PER WPB FBC 107.2.1, 107.3.5.1 AND 107.3.5.3 (13), |
| | PROVIDE THE FOLLOWING. |
| | |
| | 1. A GAS EQUIPMENT SCHEDULE LISTING BTU REQUIREMENTS |
| | FOR EACH, QUANTITIES AND TOTAL BTUS FOR THE SYSTEM. |
| | |
| | 2. SPECIFY TYPE OF GAS AND SERVICE PRESSURE AT THE |
| | METER/REGULATOR. |
| | |
| | 3. PROVIDE AND SCHEDULE AN MANUFACTURER'S OUTDOOR VENT |
| | KIT FOR EACH SCHEDULED TANKLESS GAS WATER HEATER. |
| | |
| | 4. PROVIDE COMBUSTION AIR CALCULATIONS FOR THE INDOOR |
| | GAS APPLIANCE(S) AS APPLICABLE PER FBC FG 304.1 AND FBC |
| | RES G2407.1. |
| | |
| | 5. SUBMIT ON THE ISOMETRIC DRAWING THE LENGTH OF ALL |
| | HORIZONTAL AND VERTICAL CUT SECTIONS OF PIPE PER FBC FG |
| | 402.4.1, 402.4.2, FBC RES G2413.4.1 AND G2413.4.2. |
| | |
| | 6. SPECIFY TYPE OF PIPE MATERIAL ABOVE AND BELOW GROUND |
| | BEING INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING |
| | EHD NUMBER OF CORRUGATED STAINLESS STEEL TUBING (IF |
| | APPLICABLE) FOR EACH PIPE SIZE. LIST TABLES (FBC FG |
| | 402, FBC RES G2413) FOR EACH MATERIAL USED FOR |
| | CALCULATIONS OF PIPE SIZES. |
| | |
| | 7. SHOW COMPLIANCE WITH ELECTRICAL BONDING PER FBC FG |
| | 310 AND FBC RES G2411. |
| | |
| | 8. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, TO THE |
| | MOST REMOTE OUTLET IN THE SYSTEM PER THE FBC FG |
| | 402.4.1, 402.4.2, 402.4.3 OR FBC RES G2413.4.1, |
| | G2413.4.2. |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | |