| Notes |
| Date |
Text |
| 2022-11-03 06:21:58 | 3RD REVIEW FMC | | | PERMIT: 22081267 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE OUTDOOR AIR WAS ADJUSTED TO MEET THE | | | REQUIREMENTS OF FMC 403.33.1.1. IT APPEARS THE CFM???S | | | ARE REFLECTED AT THE CEILING DIFFUSERS IN THE ROOMS BUT | | | THE VAV???S DO NOT REFLECT THE ADDITIONAL SUPPLY AIR | | | THAT HAS CHANGED FROM THE PREVIOUS DRAWING. PLEASE SHOW | | | VAV???S THAT SUPPORT THE CFM???S OF THE DIFFUSERS THEY | | | ARE SERVING. FBC 107.3.5 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|