Plan Review Notes
Plan Review Notes For Permit 22081267
Permit Number 22081267
Review Stop M
Sequence Number 2
Notes
Date Text
2022-10-07 08:41:50THE OUTDOOR AIR CALCULATIONS MUST BE CALCULATED
 ACCORDING TO FMC 403.3.1.1 AND TABLE 403.3.1.1 AND NOT
 BY THE ARCHITECT'S OCCUPANCY COUNT. PLEASE PROVIDE THE
 OUTDOOR AIR CALCULATIONS ACCORDING TO FMC 403.3.1.1,
 THE CALCULATIONS PROVIDED ARE LOW FOR THE SPACES.
  