| Plan Review Notes For Permit 22081267 |
| Permit Number |
22081267 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-10-07 08:41:50 | THE OUTDOOR AIR CALCULATIONS MUST BE CALCULATED | | | ACCORDING TO FMC 403.3.1.1 AND TABLE 403.3.1.1 AND NOT | | | BY THE ARCHITECT'S OCCUPANCY COUNT. PLEASE PROVIDE THE | | | OUTDOOR AIR CALCULATIONS ACCORDING TO FMC 403.3.1.1, | | | THE CALCULATIONS PROVIDED ARE LOW FOR THE SPACES. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|