Plan Review Notes
Plan Review Notes For Permit 22081267
Permit Number 22081267
Review Stop M
Sequence Number 1
Notes
Date Text
2022-09-06 09:21:241ST REVIEW FMC
 PERMIT: 22081267
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE INFORMATION FOR THE VAV FOE THE CONFERENCE
 ROOM. FBC 107.3.5
  
 2) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH USE OF
 SPACE; OFFICE, CONFERENCE ROOM, RECEPTION AREA,
 BREAKROOM AND STORAGE. FMC 403.3.1.1 AND TABLE
 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  