| Plan Review Notes For Permit 22081224 |
| Permit Number |
22081224 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-12-14 06:38:39 | CONTRACTOR RESUBMITTED DATA AS REQUESTED FOR FLOORING, | | | FIRE PERFORMANCE, CHANGE TO PSSS | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | | | 2022-09-22 10:15:31 | FIRE COMMENT: | | | | | | PROVIDE THE FIRE PERFORMANCE TEST DATA TO INCLUDE THE | | | CRITICAL RADIANT FLUX FOR THE PROPOSED NEW VINYL FLOOR | | | AND UNDERLAYMENT. | | | | | | NFPA 101, 10.2.7 | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|