Plan Review Notes
Plan Review Notes For Permit 22081215
Permit Number 22081215
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-08-30 15:15:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET FP 04 S - THERE IS AN INDICATION OF A ROOF
 MANIFOLD AT THE SOUTHERN END OF THE ROOF TOP THAT IS
 TOO FAR REMOTELY LOCATED.
  
 THAT MANIFOLD NEEDS TO BE RELOCATED TO SOME WHERE
 TOWARDS THE CENTER OF THE ROOF, AROUND/NEAR THE # 7
 SECTION LINE ACCESSIBLE FROM THE ROOF TRAVEL PATH.
  
 FF'S WOULD HAVE DIFFICULTY ACCESSING THE MANIFOLD IN
 THE EVENT OF AN INCIDENT AROUND THAT AREA.
  
 PER NFPA 14
  
 CH 1
  
 1.3.2 IN THOSE CASES WHERE THE AUTHORITY HAVING
 JURISDICTION
 DETERMINES THAT THE EXISTING SITUATION PRESENTS AN
 UNACCEPT ABLE DEGREE OF RISK, THE AUTHORITY HAVING
 JURISDICTION SHALL BE
 PERMITTED TO APPLY RETROACTIVELY ANY PORTIONS OF THIS
 STANDARD
 DEEMED APPROPRIATE.
  
 CONFER WITH THE OFFICE OF THE FIRE MARSHAL SHOULD YOU
 NEED TO LOCATE ACCURATELY.
  
  
  
 2) SHEET FP 06 S - ALL FIRE LINE UNDERGROUND SHALL BE
 INSTALLED PER NFPA 24 UNDER SEPARATE PERMIT, SHOP
 DRAWINGS AND MANUFACTURE'S SPECIFICATIONS.
  
 DO NOT COVER ANY FIRE LINE JOINTS PRIOR TO FIRE
 INSPECTION APPROVAL.
  
 THIS PERMIT IS IN ADDITION TO AND SEPARATE FROM AN
 ENGINEERING PERMIT.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT
  
  
 2A) PLEASE ENSURE THAT THE FDC'S WILL INSTALLED WITHIN
 100' OF A FDC PER NFPA 14.
  
 PROVIDE A NOTE OF ACKNOWLEDGMENT AND THE APPROX. THE
 DIMENSION.
  
  
  
 3) SHEET FP 01 .S - UNDER GENERAL NOTES # 1, E THERE IS
 AN INDICATION OF THE MARRIOTT INTERNATIONAL DESIGN
 STANDARDS.
  
 FOR CLARIFICATION PURPOSES, IS THIS A CORRECT NOTE AND
 DOES IT APPLY TO THIS OCCUPANCY?
  
  
  
 4) SHEET FP 05 .S - THERE ARE INDICATIONS OF AN
 ELECTRIC FIRE PUMP.
  
 PLEASE CONFIRM THAT THIS ELECTRIC FIRE PUMP WILL BE
 CONNECTED TO AN ALTERNATE POWER SOURCE, I.E. EMERGENCY
 GENERATOR. IN THE EVENT OF POWER LOSS INCLUDING THE
 FUEL SOURCE OF THIS GENERATOR.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  