Plan Review Notes
Plan Review Notes For Permit 22081212
Permit Number 22081212
Review Stop B
Sequence Number 3
Notes
Date Text
2022-10-28 11:18:55ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW TOILET GRAB BAR MAXIMUM HEIGHT TO THE
 TOP OF THE GRIPPING SURFACE ( NOT TO THE CENTER OF THE
 GRAB BAR) - FBC A 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
  
 2) THE TOILET REAR GRAB BAR IS SHOWN WITH 6 INCHES FROM
 THE SIDE WALL - SINCE THE TOILET HAS A DIMENSION RANGE
 (16 TO 18 INCHES FROM THE SIDE WALL) THE 6 INCHES SHOWN
 MAY BE INCORRECT - PLEASE REMOVE THE 6 INCHES AND SHOW
 THE TOILET REAR GRAB BAR DIMENSIONS FROM THE CENTER OF
 THE TOILET PER FBC A 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.