Plan Review Notes
Plan Review Notes For Permit 22081212
Permit Number 22081212
Review Stop P
Sequence Number 2
Notes
Date Text
2022-10-13 10:30:491ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. ADDRESSED
  
 ----UNLESS YOU CAN SHOW TECHNICAL INFEASIBILITY
 (REFERENCE 202.3 OF THE FLORIDA ACCESSIBILITY CODE),
 PER 806.1 OF THE EXISTING BUILDING CODE SAYS YOU MUST
 PROVIDE ACCESSIBILITY COMPONENTS---COMMENTS 2 AND 3
 MUST BE ADDRESSED
  
 2. PER WPB FBC 107.2.1 AND FBC EX 806.1, INDICATE ON
 THE PLANS THE EXISTING ACCESSIBLE TOILET ROOMS AND
 SINKS (WHERE SINKS ARE PROVIDED, AT LEAST 5 PERCENT,
 BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED IN EACH
 ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606 PER FBC
 ACC 213.2). PER FBC EX 806.1, THE FACILITY SHALL COMPLY
 WITH FBC ACC.
  
 3. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 FOR EXISTING ACCESSIBLE TOILET ROOMS AND EXISTING
 ACCESSIBLE SINKS.
  
 4. ADDRESSED
  
 5. ADDRESSED
  
 6. ADDRESSED
  
 7. ADDRESSED
  
 8. ADDRESSED
  
 9. ADDRESSED
  
 10. ADDRESSED
  
 11. 2020 FPC - 607.1.1 TEMPERATURE LIMITING MEANS - THE
 THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE THE
 LIMITING DEVICE FOR HOT WATER DELIVERY. PLEASE PROVIDE
 A DETAIL FOR A LIMITING DEVICE FOR THE PURPOSE OF HOT
 WATER DELIVERY. THIS WOULD BE IN ADDITION TO THE
 REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC HANDWASHING
 607.1.2/419.5. AND, THE DEVICE SHALL BE INSTALLED AT
 THE HOT WATER SOURCE PER 613.1.
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
  
  
  
  
  
  
  