| 2022-10-13 10:30:49 | 1ST PLUMBING REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. ADDRESSED |
| | |
| | ----UNLESS YOU CAN SHOW TECHNICAL INFEASIBILITY |
| | (REFERENCE 202.3 OF THE FLORIDA ACCESSIBILITY CODE), |
| | PER 806.1 OF THE EXISTING BUILDING CODE SAYS YOU MUST |
| | PROVIDE ACCESSIBILITY COMPONENTS---COMMENTS 2 AND 3 |
| | MUST BE ADDRESSED |
| | |
| | 2. PER WPB FBC 107.2.1 AND FBC EX 806.1, INDICATE ON |
| | THE PLANS THE EXISTING ACCESSIBLE TOILET ROOMS AND |
| | SINKS (WHERE SINKS ARE PROVIDED, AT LEAST 5 PERCENT, |
| | BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED IN EACH |
| | ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606 PER FBC |
| | ACC 213.2). PER FBC EX 806.1, THE FACILITY SHALL COMPLY |
| | WITH FBC ACC. |
| | |
| | 3. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS |
| | FOR EXISTING ACCESSIBLE TOILET ROOMS AND EXISTING |
| | ACCESSIBLE SINKS. |
| | |
| | 4. ADDRESSED |
| | |
| | 5. ADDRESSED |
| | |
| | 6. ADDRESSED |
| | |
| | 7. ADDRESSED |
| | |
| | 8. ADDRESSED |
| | |
| | 9. ADDRESSED |
| | |
| | 10. ADDRESSED |
| | |
| | 11. 2020 FPC - 607.1.1 TEMPERATURE LIMITING MEANS - THE |
| | THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE THE |
| | LIMITING DEVICE FOR HOT WATER DELIVERY. PLEASE PROVIDE |
| | A DETAIL FOR A LIMITING DEVICE FOR THE PURPOSE OF HOT |
| | WATER DELIVERY. THIS WOULD BE IN ADDITION TO THE |
| | REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC HANDWASHING |
| | 607.1.2/419.5. AND, THE DEVICE SHALL BE INSTALLED AT |
| | THE HOT WATER SOURCE PER 613.1. |
| | |