| 2022-09-06 11:11:51 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22081212 2007 PALM BEACH LAKES BLVD |
| | |
| | 1ST REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. PER WPB FBC 107.2.1, PROVIDE A FRONT AND SIDE |
| | ELEVATION VIEW OF THE DRINKING FOUNTAIN. COMPLY WITH |
| | FBC ACC 602.1, 602.2, 602.3, 602.4, 602.5, 602.7, 306.2 |
| | AND 306.3. |
| | |
| | 2. PER WPB FBC 107.2.1 AND FBC EX 806.1, INDICATE ON |
| | THE PLANS THE EXISTING ACCESSIBLE TOILET ROOMS AND |
| | SINKS (WHERE SINKS ARE PROVIDED, AT LEAST 5 PERCENT, |
| | BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED IN EACH |
| | ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606 PER FBC |
| | ACC 212.3). PER FBC EX 806.1, THE FACILITY SHALL COMPLY |
| | WITH FBC ACC. |
| | |
| | 3. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS |
| | FOR EXISTING ACCESSIBLE TOILET ROOMS AND EXISTING |
| | ACCESSIBLE SINKS. |
| | |
| | 4. P-0.1/STAFF LOUNGE ROOM SINK DETAIL/NOTE 5: |
| | ***A) WILKENS 740 BACKFLOW PREVENTER COMPLIES WITH ASSE |
| | 1022 FOR CARBONATED BEVERAGES. PER FBC PL 608.17.1.2, |
| | PROVIDE A LEAD FREE BACKFLOW PREVENTER WHICH COMPLIES |
| | WITH ASSE 1024 |
| | ***B) PER FBC PL 608.17.1, THE BACKFLOW PREVENTER SHALL |
| | BE INSTALLED IN THE DEDICATED LINE TO THE COFFEE MAKER |
| | |
| | 5. P-0.1/STAFF LOUNGE ROOM SINK DETAIL: PER FBC PL |
| | 606.2, PROVIDE SEPARATE SHUT-OFF VALVES FOR THE |
| | REFRIGERATOR AND THE COFFEEMAKER. |
| | |
| | 6. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE |
| | LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1. |
| | PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE |
| | SAME. |
| | |
| | 7. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH |
| | A NOTE STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN |
| | ACCORDANCE WITH FBC PL TABLE 308.5." |
| | |
| | 8. PER WPB FBC 107.2.1, PROVIDE DETAIL OF RELOCATED |
| | WATER HEATER SHOWING HEATER W/STORAGE CAPACITY, PIPING |
| | INCLUDING CW, HW, VALVES (INCLUDING VACUUM RELIEF VALVE |
| | IF APPLICABLE FBC PL 504.2) , EXPANSION TANK OR THERMAL |
| | EXPANSION RELIEF VALVE (INCLUDING SIZE), T&P DISCHARGE |
| | (INCLUDING TERMINATION) AND WATER HEATER PAN AND DRAIN |
| | (INCLUDING TERMINATION) PER WPB FPC 107.2.1; COMPLY |
| | WITH FBC PL 607.3, 503.1, 504.1, 504.4, 504.4.1, 504.5, |
| | 504.6, 504.7, 504.7.1 AND 504.7.2. |
| | |
| | 9. PER WPB FBC 107.2.1, PROVIDE DETAIL OF RELOCATED HOT |
| | WATER RECIRCULATING PUMP; SHOW INTEGRATION WITH WATER |
| | HEATER. INCLUDE ALL VALVES AND CONTROLS |
| | |
| | 10. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL |
| | ON THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM |
| | THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW |
| | SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT |
| | AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR |
| | SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS |
| | WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED |
| | SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE |
| | FOR FINAL INSPECTION. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |