| Date |
Text |
| 2022-11-21 06:20:29 | 3RD GAS REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMENDS 107.2.1 - YOU ARE STILL QUOTING THE |
| | WRONG GAS CHART. THE PIPE IS PE AND THE CHART IS FOR |
| | METALLIC. ALSO, IF USING THAT CHART, REGARDLESS OF |
| | MATERIAL, THE BTU LOAD FOR 3/4" PIPE AT 50' (151K) IS |
| | LOWER THAN THE BTU DEMAND (199K). PLEASE CHOOSE THE |
| | RIGHT CHART FOR THE MATERIAL AND PRESSURE. |
| | |
| | 2. 2017 WPB AMENDS 107.2.1 - THE ADDRESS ON THE DRAWING |
| | IS NOT CORRECT. |
| | |
| | 3. 2017 WPB AMENDS 107.2.1 - PLEASE HAVE THE PERSON WHO |
| | DESIGNED THE DRAWING PRINT THEIR NAME, SIGN THEIR NAME, |
| | AS WELL AS PUT YOUR CONTRACTOR NUMBER ON THE DRAWING AS |
| | REQUIRED BY THE WEST PALM BEACH AMENDMENTS TO CHAPTER |
| | 1. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |