Plan Review Notes
Plan Review Notes For Permit 22081153
Permit Number 22081153
Review Stop B
Sequence Number 3
Notes
Date Text
2023-07-06 13:57:22FINAL ELEVATION CERTIFICATE
 REVIEW COMMENTS
  
 3RD REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [NOT RESOLVED. REMOVE THE 1792 AND ENTER 2800 IN THE
 SPACE. REMOVE THE NOTE ABOUT THE 2800 SQFT. THIS IS
 EXPLAINED IN THE COMMENT SECTION OF SECTION D.] FOR
 ITEM A8 C) ENTER THE TOTAL COVERAGE AREA OR RATED AREA
 OF THE ENGINEERED OPENINGS WHICH IS EQUIVALENT TO THE
 PERFORMACE THAT WOULD BE PROVIDED BY THAT NUMBER OF
 SQUARE INCHES OF NON-ENGINEERED OPENINGS. THE FLOOD
 VENT DETAIL ON THE ARCHITECTURAL PLANS SPECIFY (14)
 SMART VENTS MODEL NUMBER 1540-520, WHICH HAVE A
 CAPACITY OF 200 SQFT PER VENT. THE TOTAL WILL BE 14 X
 200 = 2800. THE CRAWL SPACE AREA IS 2771 SQFT. FEMA
 TECHNICAL BULLETIN #1 SECTION 9.3.5
  
 2) RESOLVED.
  
 6) RESOLVED.
  
  
  