| Plan Review Notes For Permit 22081153 |
| Permit Number |
22081153 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2023-07-06 13:57:22 | FINAL ELEVATION CERTIFICATE | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) [NOT RESOLVED. REMOVE THE 1792 AND ENTER 2800 IN THE | | | SPACE. REMOVE THE NOTE ABOUT THE 2800 SQFT. THIS IS | | | EXPLAINED IN THE COMMENT SECTION OF SECTION D.] FOR | | | ITEM A8 C) ENTER THE TOTAL COVERAGE AREA OR RATED AREA | | | OF THE ENGINEERED OPENINGS WHICH IS EQUIVALENT TO THE | | | PERFORMACE THAT WOULD BE PROVIDED BY THAT NUMBER OF | | | SQUARE INCHES OF NON-ENGINEERED OPENINGS. THE FLOOD | | | VENT DETAIL ON THE ARCHITECTURAL PLANS SPECIFY (14) | | | SMART VENTS MODEL NUMBER 1540-520, WHICH HAVE A | | | CAPACITY OF 200 SQFT PER VENT. THE TOTAL WILL BE 14 X | | | 200 = 2800. THE CRAWL SPACE AREA IS 2771 SQFT. FEMA | | | TECHNICAL BULLETIN #1 SECTION 9.3.5 | | | | | | 2) RESOLVED. | | | | | | 6) RESOLVED. | | | | | | | | | |
|