| Plan Review Notes For Permit 22081153 |
| Permit Number |
22081153 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-06-07 14:26:12 | FINAL ELEVATION CERTIFICATE | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FOR ITEM A8 C) ENTER THE TOTAL COVERAGE AREA OR | | | RATED AREA OF THE ENGINEERED OPENINGS WHICH IS | | | EQUIVALENT TO THE PERFORMACE THAT WOULD BE PROVIDED BY | | | THAT NUMBER OF SQUARE INCHES OF NON-ENGINEERED | | | OPENINGS. THE FLOOD VENT DETAIL ON THE ARCHITECTURAL | | | PLANS SPECIFY (14) SMART VENTS MODEL NUMBER 1540-520, | | | WHICH HAVE A CAPACITY OF 200 SQFT PER VENT. THE TOTAL | | | WILL BE 14 X 200 = 2800. THE CRAWL SPACE AREA IS 2771 | | | SQFT. FEMA TECHNICAL BULLETIN #1 SECTION 9.3.5 | | | | | | 2) THE PHOTOS THAT WERE SUBMITTED ONLY SHOW FLOOD VENTS | | | ON ONE WALL. PROVIDE PHOTOS THAT SHOW THE FLOOD VENTS | | | ON AT LEAST TWO OF THE ELEVATIONS. | | | | | | 6) THE PHOTOS NEED TO STATE "RIGHT SIDE VIEW" AND "LEFT | | | SIDE VIEW" PER INSTRUCTIONS. NOT SOUTH SIDE OR WEST | | | SIDE. FEMA ELEVATION CERTIFICATE INSTRUCTIONS | | | | | | | | | |
|